About 1756-IR6I
The 1756-IR6I module provides two data formats such as integer mode and the floating-point mode. When choosing the integer mode, the integrated features are multiple input ranges, notch filter, and real-time sampling. The floating mode includes all these features with the addition of temperature linearization, process alarms, rate alarms, and digital filtering. It also has selectable temperature unit to such as Celsius or Fahrenheit. There are Four (4) possible input ranges for the module including 1 to 487 m?, 2 to 1000 m?; 4 to 2000 m?;, and 8 to 4000 m?;. These ranges designate the minimum and maximum signals detectable by the module. It has Six (6) individually isolated RTD inputs and a resolution of 16 bits. Actual resolution includes 7.7 m?bit for 1-487 Ohms; 15 m?/bit for 2-1000 Ohms, 30 m?/bit for 4 - 2000 Ohms and 60 m?/bit for 8 - 4020 Ohms. The module’s notch filter line noise filtering. Make sure to choose the filter that closely matches the application’s anticipated noise frequency. The digital filter smoothens data by eliminating noise transients on each input channel.
The 1756-IR6I’s real-time sampling feature lets the module multicast data it gathered from scanning all of its input channels. To enable multicast, configure Real-Time Sampling (RTS) period and a Requested Packet Interval (RPI) period.
The Allen-Bradley 1756-IR6I is an ControlLogix module that is used to receive signals from Resistance Temperature Detectors (RTD). This module belongs to the analog input category and especially used for Temperature measurement applications.
The overall input resolution of this module is 16 Bits. In actual measurement, this translates to 7.7 m?/bit for 1…487 ?; 15 m?/bit for 2…1000 ?; 30 m?/bit for 4…2000 ? and 60 m?/bit for 8…4020 ?.
is a professional industrial automation components and etc. Want to know more about industrial automation products list