Application:
ASSEN ACP portable Current transformer analyzer is mainly used for field or lab testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt 7 inch touch TFT LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The CT PT Analyzer is the most complete and easy-to-use testing system for protection and metering CTs according to IEEE and IEC standards.
Functions:
CT(Current Transformer):
1. Excitation Characteristic Test
2. Auto Calculation of Knee Point Value
3. Auto 5% and 10% error curves, can measure ALF
4. Transformer Ratio Test
5. Polarity
6. Ratio difference measurement
7. Phase (angle difference) measurement
8. Primary Current Injecting
9. Withstand Test of Power Frequency Alternating Current
10. Secondary Load Test
11. Secondary Winding Test
12. Measuring the volt-ampere characteristics of medium and low voltage CTs and zero sequence CTs
13. Measure GIS, casing CT
14. Comprehensive test, complete excitation and transformation ratio polarity at the same time in one test
PT(Voltage Transformer)
1.Excitation Characteristic Test
2. Auto Calculation of Knee Point Value
3. Transformer Ratio Test
4. Polarity
5. Ratio difference measurement
6. Phase (angle difference) measurement
7. Withstand Test of Power Frequency Alternating Current
8. Actual Secondary Load Test
9. Secondary Winding Test
No. |
Item Name |
ACP Current Transformer and Voltage Transformer CT PT Analyzer |
1 |
Test standards |
IEC60044-1, IEC60044-6, GB1208, GB16847, C57.13 |
2 |
Power supply |
AC220V±10%,50Hz/60Hz±10% |
3 |
Power output |
0.1~125V (AC) |
4 |
Current output |
0.001~5A(RMS) |
5 |
Power output |
300VA |
6 |
Max. knee voltage measurement |
45kv |
7 |
Current measurement range |
0~10A (automatically change range in 0.1/0.4/2/10A) |
8 |
Current measurement error |
<±0.1%+0.01%FS |
9 |
Voltage measurement range |
0~200 V (automatically change range in 1V/10V/70V/200V) |
10 |
Voltage measurement error |
< ±0.1%+0.01%FS |
11 |
Turns ratio measurement range |
1~30000; 1~2000 error<0.05%; 2000~5000 error>0.1%; 5000~35000 error<0.2% |
12 |
Phase measurement |
error: ±2min,resolution:0.01min |
13 |
Coil resistance measurement |
Range: 0~8kΩ(automatically change range in 2ohm /20ohm /80ohm/800ohm/8kohm) Error< 0.2%RDG+0.02%FS Maximum resolution: 0.1mΩ |
14 |
Temperature measurement |
-50~100 Celsius degree, error<3 Celsius degree |
15 |
CT Secondary burden |
Range 0-160ohm (automatically change range in 2ohm/ 20ohm/80ohm/160ohm) Error<0.2%RDG+0.02%FS Maximum resolution 0.001ohm |
16 |
PT Secondary burden |
Range 0-80kohm (automatically change range in 800ohm / 8kohm /80kohm) Error<0.2%RDG+0.02%FS Maximum resolution: 0.1ohm |
17 |
PT ratio measurement |
Range: 1~30000 1~5000 error<0.2% 5000~30000 error<0.5% |
18 |
Saved data groups |
>1000groups |
19 |
Work condition |
Temperature: -10℃-50℃, moist: ≤90% |
20 |
Size |
485mm*356mm*183mm |
21 |
Weight |
<15Kg |
Please contact ASSEN for more details.