MODEL |
NX9 |
NX7 |
NX2 |
NX3 |
NX4 |
NX1 |
Appearance (mm) |
|
|
|
|
|
|
Function |
ㆍFuzzy |
ㆍAuto tuning |
ㆍExternal contact input |
ㆍHeater Break Alarm(HBA1) |
ㆍInput filter : OFF, 1~120sec |
ㆍZone PID |
ㆍ2 Alarm outputs |
ㆍOutput Limitation |
ㆍInterface(RS/485/422) |
ㆍRetransmission output (PV, SV, MV) |
ㆍGroup PID |
ㆍUniversal-input/output |
ㆍHeating/Cooling control |
ㆍIP 65 front facia |
ㆍHeating/Cooling hysteresis |
|
|
Input |
Thermocouple : K, J, E, T, R, S, B, L, N, U, WRe 5-26, PL-II |
R.T.D : Pt 100Ω, KPt 100Ω |
Direct voltage : 1~5V, 1~10V, -0~20mV, 0~100mV --------------(Free scale type) |
|
Sampling cycle |
250ms |
Input display resolution |
Below decimal point of Input signal and Measuring range |
Input impedance |
T/C and mV input : Min, 1MΩ DC V : 1MΩ |
Source tolerable resistance |
Thermocouple : Max. 250Ω, Voltage : Max. 2 kΩ |
Lead wire tolerable resistance |
R.T.D : Max. 150Ω / wire (notice : Identical conductor resistance between 3wires) |
Input tolerable voltage |
±10V (T/C, R.T.D, Voltage : mV DC), ±20V(Voltage : V DC) |
Noise removal rate |
NMRR(Nomal mode) : 40dB min. / CMRR(Common mode) : 120dB min.(50/60Hz ±1%) |
Standard |
T/C, R.T.D : KS, IEC, DIN |
Standard junction temp. |
±1.5°C(15~35 °C), ±2.0°C(0~50 °C) |
Burn-oup |
T/C : OFF, Up/Down selectable / R.T.D : OFF, UP selectable (Detection current : 50mA) |
Accuracy |
±0.5% (Full scale) |
Power supply for sensor |
DC 24V(Internal resistance : 1.2 kΩ) Max 50mA / DC 15V(Internal resistance : 790 °C) |
|
|
|
|
|