Specification
Standard |
KS C 4802 |
Installation |
in and Out-door |
Line Voltage |
3300V or 6600V |
Rated Voltage |
1900V or 3800V |
Rated Capacity |
33-250kvar |
Frequency |
50Hz or 60Hz |
Painting Color |
Munsell No. 5Y7/1 |
Characteristics
Ambient Air
Temperature |
-20°C ~ +40°C
(Average is below 35°C for 24h) |
Max. Permissible
Voltage |
110% for 12h in every 24h |
Max. Permissible
Current |
incase of including high frequence
being available up to 130% of ratings |
Tolerence of
Capacity |
For ratings, the deviation of each
phase -5% ~ +10%is within±3% |
Temperature Rise |
Below 20 degree at 35°C |