The CE-IJ03 1 element AC current transducer is designed to measure and monitor average RMS AC current, then produce a standard signal such as 4-20mADC, 0-5VDC and so on.
Rated input: 0-500AAC(average RMS current ; TRMS current optional)
Output signal: 0-5V;0-20mA;4-20mA;1-5V;4-20mA loop powered;0-10V; oc frequency(0-5kHZ,0-10KHZ)
Power supply: +12VDC;+15VDC;+24VDC, self power optional
Accuracy: 0.5% optional
Output ripple: 15mV
Isolation: 2500V DC
Load resistance: Voltage Output >2kohm; Current Output=250ohm
Overload capacity: 20 times or <5/sec at 500A
Temperature drift: ≤500ppm℃
Response time: ≤300ms
Operating temperature: -10℃~+60℃
Quiescent power consumption: 200~250mW(with +12VDC power )