1. Fault Indicator Parameters
Short-circuit current(Δ value):100A~400A settable;
Fault indication mode: LED light flashing;
Fault indication LED light flashing visual range: 300m (night);30m (daytime: tested under 50000lx light intensity);
Low battery warning LED light flashing visual range: 200m (night);20m (daytime: tested under 50000lx light intensity);
LED flashing time: >2000h (two 14505 batteries);flashing interval 50ms/5s;
Fault types: phase-to-phase short-circuit fault; single-phase grounding fault (high-resistance grounding and ungrounded system, detection signals are injected through signal sources);
Fault reset method: timing reset, power-on reset, remote manual reset;
Timing reset time: 1min~1440min settable;
Power-on current fixed value:3A
Load current telemetry range: 0~630A;
Load current telemetry accuracy: ±3A(Load current ≤100A);±3%(Load current> 100A);
Wireless working frequency: 433 MHz;
Wireless communication distance: ≥30m (visible and unobstructed);
Withstand short-circuit impulse current capability: short-circuit fault current (effective value) 16kA/2s
Power supply: 3.6V lithium battery (Brand: MOLEX, 510050200 connector), recommend to use 14505 battery,support 1 (working time halved) or 2 batteries;
Static operating current: <30uA;
Shell material: UV stable polycarbonate
Line jamming material: stainless steel
Protection level: IP67;
Size: 87mm(diameter)×174mm(height);
Weight:450g (exclude the batteries);
Features: The battery is detachable, and the 2 batteries are connected in parallel. With 1 battery it can also work normally, but the working time is halved.
System conditions:
Line frequency: 50Hz (default 50Hz, 60Hz products can also be provided, which need to be customized);
Line voltage: 6kV~35kV;
Cable diameter: 8~35mm;
Environmental conditions:
Storage temperature: -40℃~85℃
Working temperature: -40℃~70℃
Environment humidity: 5~95%RH
Maximum absolute humidity: 35g/m3
Altitude: ≤2000m