Home
/
Categories
/
Measurement & Analysis Instruments
/
Testing Equipment
/
Overhead Fault Indicator FI-3A9F
Overhead Fault Indicator FI-3A9F
FOB Price 80 USD / Unit
MOQ
1 Unit
Lead Time
20 days
China
Main Products : fault indicator, automatic circuit recloser, cable accessories, substation
Building 4, East Zone, No. 10 Xibeiwang East Road, Haidian District, Beijing, P.R. China Beijing, Beijing
Overhead Fault Indicator FI-3A9F Details
Place of Origin
China
Supply Type
In-Stock Items
Condition
New
Overhead Fault Indicator FI-3A9F Introduce

1. Fault Indicator Parameters

Short-circuit current(Δ value):100A~400A settable;

Fault indication mode: LED light flashing;

Fault indication LED light flashing visual range: 300m (night);30m (daytime: tested under 50000lx light intensity);

Low battery warning LED light flashing visual range: 200m (night);20m (daytime: tested under 50000lx light intensity);

LED flashing time: >2000h (two 14505 batteries);flashing interval 50ms/5s;

Fault types: phase-to-phase short-circuit fault; single-phase grounding fault (high-resistance grounding and ungrounded system, detection signals are injected through signal sources);

Fault reset method: timing reset, power-on reset, remote manual reset;

Timing reset time: 1min~1440min settable;

Power-on current fixed value:3A

Load current telemetry range: 0~630A;

Load current telemetry accuracy: ±3A(Load current ≤100A);±3%(Load current> 100A);

Wireless working frequency: 433 MHz;

Wireless communication distance: ≥30m (visible and unobstructed);

Withstand short-circuit impulse current capability: short-circuit fault current (effective value) 16kA/2s

Power supply: 3.6V lithium battery (Brand: MOLEX, 510050200 connector), recommend to use 14505 battery,support 1 (working time halved) or 2 batteries;

Static operating current: <30uA;

Shell material: UV stable polycarbonate

Line jamming material: stainless steel

Protection level: IP67;

Size: 87mm(diameter)×174mm(height);

Weight:450g (exclude the batteries);

Features: The battery is detachable, and the 2 batteries are connected in parallel. With 1 battery it can also work normally, but the working time is halved.

System conditions:

Line frequency: 50Hz (default 50Hz, 60Hz products can also be provided, which need to be customized);

Line voltage: 6kV~35kV;

Cable diameter: 8~35mm;

Environmental conditions:

Storage temperature: -40℃~85℃

Working temperature: -40℃~70℃

Environment humidity: 5~95%RH

Maximum absolute humidity: 35g/m3

Altitude: ≤2000m